Voltage Drop Calculator
Calculate voltage drop in a copper or aluminum wire from the AWG size, current, length and system voltage, and find the smallest wire that keeps the drop under 3%. Example: 20 amps over 100 feet of 12 AWG copper on 120 volts drops 7.90 volts, or 6.58%.
Show steps
How to use the Voltage Drop Calculator
- Choose single phase or three phase and the wire material.
- Select the wire size and enter the current and one-way length.
- Enter the system voltage.
- Press Calculate to see the drop, percent and the smallest wire that stays under 3%.
Formula and method
Single phase: VD = 2 x K x I x L / CM. Three phase: VD = 1.732 x K x I x L / CM. K is 12.9 ohm-circular-mils per foot for copper and 21.2 for aluminum, I is the current in amps, L is the one-way length in feet and CM is the wire area in circular mils. Percent drop = VD / system voltage x 100.
Worked example: 20 A, 100 ft, 12 AWG copper, 120 V
| Step | Value |
|---|---|
| 2 x 12.9 x 20 x 100 | 51,600 |
| Divide by 6,530 circular mils | 7.90 V |
| Percent of 120 V | 6.58% |
| Smallest wire for 3% or less | 8 AWG |
Circular mils by wire size
| AWG | Circular mils |
|---|---|
| 14 | 4,110 |
| 12 | 6,530 |
| 10 | 10,380 |
| 8 | 16,510 |
| 6 | 26,240 |
| 4 | 41,740 |
| 2 | 66,360 |
| 1/0 | 105,600 |
| 4/0 | 211,600 |
Reducing voltage drop
Use a larger wire, shorten the run, raise the system voltage, or reduce the load current. Copper drops less than aluminum of the same size. Always check that the wire is also rated for the current, since voltage drop and ampacity are separate limits.
Frequently asked questions
What is voltage drop?
The loss of voltage along a wire because of its resistance. It grows with current and length.
What voltage drop is acceptable?
The NEC recommends 3% or less on a branch circuit and 5% or less for the whole feeder and branch.
How do I calculate voltage drop?
Multiply 2 x K x current x one-way length, then divide by the wire circular mils.
Why use one-way length?
The formula multiplies by 2 for the return path, so you enter the one-way distance.
Is aluminum worse than copper?
Aluminum has about 64% higher resistance, so it drops more voltage for the same size.
How do I fix too much voltage drop?
Increase the wire size or shorten the run.
Sources
Related calculators
Related to This Article
More math articles
- The Ultimate 7th Grade PEAKS Math Course (+FREE Worksheets)
- 6th Grade MEAP Math FREE Sample Practice Questions
- The Best Grade 5 Math Book for Louisiana Students
- Ordering and Comparing Decimals for 4th Grade
- Free Grade 3 English Worksheets for California Students
- The Best Grade 6 ELA Practice Tests for Florida Students
- Top 10 Tips You MUST Know to Retake the TSI Math
- 6th Grade PSSA Math Practice Test Questions
- 4th Grade FSA Math Worksheets: FREE & Printable
- The Practical Benefits Of Knowing Math – The 10 Best Industries For Math Geeks


What people say about "Voltage Drop Calculator: Copper & Aluminum Wire (AWG)"?
No one replied yet.